DGH D6100 Analog Voltage Input Module

DGH D6100 Analog Voltage Input Module

The D6100 7-channel voltage input module is part of the DGH's D6000 data acquisition module family. This input module measures signal across six different voltage ranges (±25mV, ±50mV, ±100mV, ±1V, ±5V and ±10V) and continuously converts the data at the rate of up to 25 conversions per second, storing the latest result in the buffer. The data (unsigned integer percentage of full-scale values) can then be retrieved by sending a Modbus query to the module from the host processor. The D6100 voltage input module can be directly connected to a wide range of sensors and annunciators, and provides all signal conditioning and linearisation, while containing no pots or DIP switches. For extra security, it utilises a non-volatile EEPROM (Electrically Erasable Programmable Read Only Memory) to store all user-selectable settings such as the range, meaning the values are maintained in the event of power loss. The D6100 module is compatible with any commercial software supporting Modbus RTU protocol and is DIN-rail mountable (MK-1 mounting kit required). Combined with other D6000 modules, it provides the complete, customised data acquisition system for given application.

  • 7-channel differential analog voltage input module
  • Measures 6 different ranges: ±25mV, ±50mV, ±100mV, ±1V, ±5V and ±10V
  • Modbus RTU protocol
  • User-selectable features include analog input range per channel, baud rate, parity type, digital filtering and others
  • 16-bit ADC, 25/20 conversions per second (total across the enabled channels)
  • Compatible with all commercial software programs supporting Modbus RTU protocol, including programs from Wonderware, DreamReport, National Instruments Labview, Indusoft and others
  • Accuracy: ±0.05% of FS maximum
  • Span temperature coefficient: ±50ppm/°C maximum
  • Input burnout protection to 250 Vac
  • Input impedance: 20MΩ minimum
  • Power requirements: Serial = 1.4W
  • Operating temperature -25°C to +70°C
  • Mix and match with other D6000 modules to build a complete, customised data acquisition system

The applications for the D6000 data acquisition modules include:

  • Process monitoring and control
  • Remote data logging to any host computer
  • Product testing
  • Direct connection to PLC

Specifications
Additional Features
  • 16-bit ADC, 25/20 conversions per second
  • Accuracy: ±0.05% of FS maximum
  • Voltage drop: 2.0V maximum
  • Input impedance 20MΩ minimum
  • Operating temperature of -25°C to +70°C
Input/Output Analog voltage inputs
Number of channels 7 channels
Power requirements Serial 1.4W
Ranges
  • ±25mV
  • ±50mV
  • ±100mV
  • ±1V
  • ±5V
  • ±10V

We are pleased to provide you with a range of additional content including videos, product datasheets, case studies, white papers and application notes for your reference. Please see below for the latest content available:

 

 

DOCUMENTATION
PDF Document DGH D6000 Series Datasheet
PDF Document DGH D6000 Series User Manual
PDF Document Quickstart Guide for D6000 Series

This product is available fully compliant to the RoHS EU directive 2002/95/EC.

  • Views: 352
  • Product Code: DGH D6100 Analog Voltage Input Module
  • SKU: DGH D6100 Analog Voltage Input Module
  • Availability: In Stock
0 Product(s) Sold
  • £0.00
  • Ex Tax: £0.00

Tags: D6000, D 6000, D6100, D 6100